Short answer: under SMACNA practice for low-pressure galvanised ductwork, ducts up to 12 in (300 mm) use 26 gauge sheet, and the sheet gets thicker as the duct gets larger — up to 18 gauge for ducts of 61 in (1,550 mm) and over. The table below is the chart we use in our Dhahran factory.
SMACNA duct gauge chart
| Rectangular duct (longest side) | Round duct diameter | Sheet gauge | Approx. thickness (galvanised) |
|---|---|---|---|
| Up to 12 in (300 mm) | Up to 12 in | 26 | 0.55 mm |
| 13–30 in (330–760 mm) | 13–30 in | 24 | 0.70 mm |
| 31–42 in (790–1,070 mm) | 31–40 in | 22 | 0.85 mm |
| 43–60 in (1,090–1,520 mm) | 41–60 in | 20 | 1.00 mm |
| 61 in (1,550 mm) and over | 61 in and over | 18 | 1.31 mm |
Thicknesses are nominal values for galvanised sheet and are given for guidance. Always follow the project specification, pressure class and the latest SMACNA HVAC Duct Construction Standards; Saudi Aramco projects also follow SAES-K-001.

When to go heavier than the chart
- Higher pressure classes (medium and high pressure systems) need heavier gauges or closer reinforcement.
- Kitchen and fume exhaust ducts are normally specified in heavier black steel or stainless steel and welded.
- Large industrial ducts are reinforced with angle-iron flanges, external stiffeners and internal tie rods.
- Outdoor and rooftop ducts exposed to Gulf heat and sand often get a heavier sheet and extra sealing.
Joints matter as much as gauge
For most low and medium pressure ducts we use in-built TDF flanges: they are rigid, air-tight, need no welding or riveting, and install faster than angle flanges. Smaller ducts can use drive and S-cleats (SMACNA T1, T6, T11).
Need ducts made to SMACNA?
Hadaf Al Jawdah manufactures GI, stainless and black-steel ducts in Dhahran — 350–500 tonnes a month, Saudi Aramco In-Kingdom approved, with 24–48 h fast track for urgent standard ducts. See our rectangular ducts and spiral ducts, or send your BOQ to inquiry@hadafalj.com / WhatsApp +966 55 413 5857.